In-Row vs. Facility CDUs: Where the CDU Should Sit

Every liquid-cooled data hall needs a coolant distribution unit between the facility water and the racks. The harder question is where to put it. You can place CDUs in the server row as cabinets, or you can put larger units in a mechanical gallery and pipe conditioned coolant out to the hall. Both approaches work. They make different demands on your floor, your water and your maintenance team.

What each layout looks like

An in-row CDU is a cabinet that takes a rack position. Facility water reaches it through piping under the floor or overhead, and the CDU modulates its primary supply valve to control how much of that water flows through its plate heat exchanger. Its own pumps circulate the technology cooling system (TCS) loop to the racks around it. Each unit serves a defined group of racks.

A facility CDU is a larger skid that lives outside the white space, usually in a mechanical gallery. One unit can serve a whole block of racks, and several units can be linked to serve a hall. The TCS loop runs from the gallery to the rows through distribution piping.

Floor space

In-row units use white space. Every cabinet given to cooling is a cabinet that can’t hold IT. In a hall built for racks around 120 kW, the class of current liquid-cooled AI racks that trade can be worth making, because the CDU stays close to the load and the piping runs stay short.

Facility units move that equipment out of the hall. The cost shows up elsewhere. You need a gallery, and you need room to route larger pipes from it. In a new build, that space can be planned from day one. In a retrofit, the gallery may not exist.

Facility water

The water you have on the facility side narrows the choice quickly. Many in-row units are designed for clean process water or water-glycol. Facility-scale units can be built with materials and heat exchangers that tolerate seawater, river water or reclaimed water. If your site plans to use a natural water source for free cooling, check the CDU’s facility water rating before anything else.

Maintenance and redundancy

In-row designs spread risk across many smaller units. A single unit out of service affects a small group of racks, and technicians can work on it in the row. Ask how the units share load and whether one can be serviced while its neighbors carry the racks.

Facility designs concentrate capacity. That makes redundancy planning more important: how many pumps per skid, whether they run active-active or in standby, and how many linked units can drop out before the hall loses cooling. The advantage is that service work happens outside the white space, away from customer equipment.

Growth

In-row capacity grows rack group by rack group. That suits colocation operators who fit out a hall in phases or whose tenants bring different cooling needs.

Facility capacity grows in larger steps. It suits operators who know the hall will fill with one class of high-density AI hardware and want a single loop to manage.

When a mix makes sense

Some sites use both. A facility unit runs a clean facility-side loop for the building, and in-row units create isolated loops for tenants with their own fluid or pressure requirements. This is common where a colo is moving from tenant-owned cooling to owning the whole liquid loop.

Questions to settle before choosing

  • Where is there physical room: a rack position, a gallery or neither?
  • What facility water will you run, now and in five years?
  • What TCS pressure do the cold plates and manifolds need at the rack?
  • What redundancy level does your SLA require, and can units be serviced while the hall runs?
  • Will the hall fill in one phase or several?

Nautilus builds EcoCoreยฎ CDUs for both layouts: the EcoCoreยฎ RCD for in-row placement and the EcoCoreยฎ FCD for facility-scale deployment. If you are working through these questions for a specific site, talk to our engineering team about your layout and water source.

Book a CDU layout review with Nautilus engineering.