EcoCore FCD
EcoCore FCD
Facility Cooling Distribution Unit
EcoCore FCD delivers scalable, leak-proof cooling designed for high-density AI and HPC data centers. It integrates seamlessly with all liquid cooling methods, ensuring efficient, reliable performance across the entire data hall.
Benefits
Up to 4,000kW+ Heat Rejection
Handles high-density AI and HPC workloads with ease.
Leak-Proof Design
Vacuum-sealed, closed-loop system eliminates risk of leaks.
Compatible with all Cooling Methods
Supports direct-to-chip, immersion, rear-door, and hot aisle cooling.
Manufacturer Agnostic
Works with regional manufacturers to integrate with existing infrastructure, reducing delivery time.
Flexible Facility Integration
Accommodates any facility design and multiple cooling configurations for full customization.
Simplified Installation
Fully prefabricated, skidded solutions for quick repurposing of space, reducing on-site deployment and commissioning complexity.
Download the Full Product Data Sheet
Features
- Dual-Loop Configuration: EcoCore FCD utilizes a dual-loop system, with a closed loop for IT equipment cooling and an open loop for external water sources.
- Flexible Compatibility (Water Sources): EcoCore FCD supports freshwater, saltwater, graywater, and industrial water systems.
- Compact Footprint: Designed to fit seamlessly into existing data halls, maximizing space utilization without compromising cooling performance.
- Top or Bottom Water Connections: Installation flexibility with top or bottom feed options, accommodating diverse facility layouts.
- Precise Temperature Control: Delivers consistent and precise cooling to ensure optimal thermal conditions, preventing thermal shocks.
- Scalable Design: Supports parallel operation via a common hot water header and supervisory controls.
- Modular Filtration: Optional side stream and primary filters.
- Leak-Proof Operation: Vacuum-sealed, closed-loop design eliminates any risk of leaks.
- No Leak Risk: By design, EcoCore FCD cannot leak.
- Dual Power Feed: Equipped with dual power feeds for redundancy, ensuring continuous operation.
- Up to N+2 Redundancy: Ensures continued operation even in the event of multiple failures.
- Comprehensive Sensor Array: Flow, temperature, and pressure sensors across primary and secondary circuits.
- Portable Touchscreen Display: Provides real-time monitoring and control with a user-friendly interface.
- Communication Options: Supports Modbus RT, Modbus TCP, OPC UA protocols for remote control and monitoring.
- Energy Efficient: Rated at 50 kW, with a typical draw of 18 kW, reducing operational costs.
- Wide Application Range: Suitable for perimeter and full facility cooling.
EcoCore FCD Technical Specifications
Category | FCD Specifications |
---|---|
Cooling Capacity per Module | 2000 kW to 4000 kW |
Approach [ATD] | 1.5ยฐC [2.7ยฐF] |
Maximum TCS Flow | 50 L/S (793 GPM) |
TCS Pressure Head at Maximum Flow | 2.5 Bar [36 PSI] ( 6 bar [87 psi ] total available head) |
Dimensions | 2.7 m ร 1.7 m ร 2.1 m (8.9 ft ร 5.6 ft ร 6.9 ft) |
Power | 400V - 480V 50-60Hz 3-phase dual feeds |
Maximum Power Consumption | 42 kW |
Primary Coolant Type (FWS) | Process Water Natural Source Water Water-Glycol Mix [1-25%] |
Secondary Coolant Type (TCS) | Process Water Water-Glycol Mix [1-25%] |
Primary Connection | 150mm [6 in.] Sanitary, SS316 |
Secondary Connection | 150mm [6 in.] Sanitary, SS316 |
TCS Filtration | 25ฮผm Full Stream 1ฮผm Side-Stream |
FWS Filtration (Optional) | 500ยตm Full-Stream |
Redundancy | Unit or System |
Integrated Degasser | Yes |
Linked System Operation | 2 to 6 CDU Modules |
Communication | Modbus, OPC UA, SNMP, Redfish |
View Our Other Solutions
FAQs
What exactly is the EcoCore FCD and where is it used?
How much cooling capacity can one FCD unit deliver?
Each FCD module supports between 2,000 kW and 4,000 kW of heat rejection, enabling it to support dense computing loads and facility-scale deployments.
How does the EcoCore FCD manage leaks and reliability concerns?
The FCD features our patented variable leak prevention system (LPS) it uses a vacuum-sealed, closed-loop design that ensures leak-proof operation. It is engineered so that it inherently cannot leak and incorporates redundancy up to N+2 for critical systems.
Is EcoCore FCD compatible with my facilityโs cooling and water systems?
Yes. The FCD is water-source agnostic, designed to support freshwater, saltwater, graywater, or industrial water sources. It works alongside direct-to-chip, immersion, rear-door, hot-aisle, or other cooling architectures.
What are the technical specs: connections, flow, controls, and footprint?
The FCD supports a maximum TCS flow of 50 L/s (โ793 GPM) and a pressure head of 2.5 bar (with total available head up to 6 bar). It uses 150 mm (6 inch) SS316 sanitary connections for both primary and secondary circuits. Approach temperature difference (ATD) is 1.5 ยฐC (2.7 ยฐF). For controls, it supports Modbus, OPC UA, SNMP, and Redfish protocols, and comes with built-in sensors, a touchscreen display, and modular filtration options.
Join the
Liquid-Cooling Revolution
EcoCore CDUs not only simplify selecting your data center cooling methods, but provide better compatibility, scalable efficiency, and flexibility to exceed sustainability goals now and later. Ready to step into the future?