EcoCore RCD
Compact, High-Density Cooling at the Rack Level
EcoCore RCD
In-row Cooling Distribution Unit
The EcoCore RCD is Nautilus’s in-row Cooling Distribution Unit, designed to deliver localized, high-capacity cooling directly to the row or perimeter. With up to 2,000 kW of heat rejection in just 1.2 m² of space, the RCD supports liquid-to-liquid (L2L) cooling for AI-ready deployments where footprint and scalability are critical. Featuring adaptable flow and pressure ranges, thermal load balancing across linked units, and built-in redundancy, the RCD enables operators to efficiently cool today’s densest compute clusters while future-proofing for tomorrow’s workloads.
Benefits
Space-Efficient Performance
Achieves 129 kW per ft² of cooling density
AI-Ready Flexibility
Supports both L2L and L2A cooling methods
Scalable Deployment
Modular design with thermal load balancing across units
Fast Provisioning
Compact, prefabricated form factor accelerates time-to-deployment
Proven Reliability
Built-in redundancy for pumps and filtration ensures uptime
Versatile Placement
Fits in-row, end-of-row, or mechanical gallery configurations
Download the Full Product Data Sheet
Features
- Compact footprint (1.2 m²) for space-constrained environments
- Modular scalability for row, pod, or small data hall cooling
- Redundant pump and filtration systems ensure continuous operation
- Adaptable flow and pressure ranges to meet evolving workload demands
- Thermal load balancing across grouped RCD units
- Local and remote HMI for monitoring and system control
- Integration via Modbus, OPC UA, and SNMP and Redfish
- Intelligent load distribution across multiple CDUs
- Heat rejection range from 300 kW up to 2,000 kW per unit
- Compact footprint delivering 129 kW per ft² (0.3 m²)
- Optimized for targeted AI and HPC cluster deployments
EcoCore RCD Technical Specifications
Category | RCD Specifications |
---|---|
Cooling Capacity per Module | 300kW to 2500 kW |
Approach [ATD] | 4°C [7.2°F] |
Maximum TCS Flow | 60 L/S (951 GPM) |
TCS Pressure Head at Maximum Flow | 2.3 Bar [33 PSI] ( 5 bar [73 psi ] total available head) |
Dimensions | 1.2 m × 1.2 m × 2.3 m (3.9 ft × 3.9 ft × 7.6 ft) |
Power | 400V - 480V 50-60Hz 3-phase dual feeds |
Maximum Power Consumption | 32kW |
Primary Coolant Type (FWS) | Process Water Water-Glycol Mix [1-25%] |
Secondary Coolant Type (TCS) | Process Water Water-Glycol Mix [1-25%] |
Primary Connection | 150 mm [6 in.] Sanitary, SS316 |
Secondary Connection | 150 mm [6 in.] Sanitary, SS316 |
TCS Filtration | 25µm Full-Stream |
FWS Filtration (Optional) | 500µm Full-Stream |
Redundancy | N+1 Pump and Filter |
Integrated Degasser | Yes |
Linked System Operation | 2 to 6 CDU Modules |
Communication | Modbus, OPC UA, SNMP, Redfish |
View Our Other Solutions
Join the
Liquid-Cooling Revolution
EcoCore CDUs not only simply select your data center cooling methods, but provide better compatibility, scalable efficiency, and flexibility to exceed sustainability goals now and later. Ready to step into the future?