EcoCore RCD

Compact, High-Density Cooling at the Rack Level

EcoCore RCD

In-row Cooling Distribution Unit

The EcoCore RCD is Nautilus’s in-row Cooling Distribution Unit, designed to deliver localized, high-capacity cooling directly to the row or perimeter. With up to 2,000 kW of heat rejection in just 1.2 m² of space, the RCD supports liquid-to-liquid (L2L) cooling for AI-ready deployments where footprint and scalability are critical. Featuring adaptable flow and pressure ranges, thermal load balancing across linked units, and built-in redundancy, the RCD enables operators to efficiently cool today’s densest compute clusters while future-proofing for tomorrow’s workloads.

Benefits

Space-Efficient Performance

Achieves 129 kW per ft² of cooling density

AI-Ready Flexibility

Supports both L2L and L2A cooling methods

Scalable Deployment

Modular design with thermal load balancing across units

Fast Provisioning

Compact, prefabricated form factor accelerates time-to-deployment

Proven Reliability

Built-in redundancy for pumps and filtration ensures uptime

Versatile Placement

Fits in-row, end-of-row, or mechanical gallery configurations

Download the Full Product Data Sheet

Features

  • Compact footprint (1.2 m²) for space-constrained environments
  • Modular scalability for row, pod, or small data hall cooling
  • Redundant pump and filtration systems ensure continuous operation
  • Adaptable flow and pressure ranges to meet evolving workload demands
  • Thermal load balancing across grouped RCD units
  • Local and remote HMI for monitoring and system control
  • Integration via Modbus, OPC UA, and SNMP and Redfish
  • Intelligent load distribution across multiple CDUs
  • Heat rejection range from 300 kW up to 2,000 kW per unit
  • Compact footprint delivering 129 kW per ft² (0.3 m²)
  • Optimized for targeted AI and HPC cluster deployments

EcoCore RCD Technical Specifications

Category RCD Specifications
Cooling Capacity per Module 300kW to 2500 kW
Approach [ATD] 4°C [7.2°F]
Maximum TCS Flow 60 L/S (951 GPM)
TCS Pressure Head at Maximum Flow 2.3 Bar [33 PSI] ( 5 bar [73 psi ] total available head)
Dimensions 1.2 m × 1.2 m × 2.3 m
(3.9 ft × 3.9 ft × 7.6 ft)
Power 400V - 480V 50-60Hz
3-phase dual feeds
Maximum Power Consumption 32kW
Primary Coolant Type (FWS) Process Water
Water-Glycol Mix [1-25%] 
Secondary Coolant Type (TCS) Process Water
Water-Glycol Mix [1-25%]
Primary Connection 150 mm [6 in.]
Sanitary, SS316
Secondary Connection 150 mm [6 in.]
Sanitary, SS316
TCS Filtration 25µm Full-Stream
FWS Filtration (Optional) 500µm Full-Stream
Redundancy N+1 Pump and Filter
Integrated Degasser Yes
Linked System Operation 2 to 6 CDU Modules
Communication Modbus, OPC UA,
SNMP, Redfish