EcoCore RCD
Compact, High-Density Cooling at the Rack Level
EcoCore RCD
In-row Cooling Distribution Unit
Benefits
Space-Efficient Performance
Achieves 129 kW per ft² of cooling density
AI-Ready Flexibility
Supports both L2L and L2A cooling methods
Scalable Deployment
Modular design with thermal load balancing across units
Fast Provisioning
Compact, prefabricated form factor accelerates time-to-deployment
Proven Reliability
Built-in redundancy for pumps and filtration ensures uptime
Versatile Placement
Fits in-row, end-of-row, or mechanical gallery configurations
Download the Full Product Data Sheet
Features
- Compact footprint (1.2 m²) for space-constrained environments
- Modular scalability for row, pod, or small data hall cooling
- Redundant pump and filtration systems ensure continuous operation
- Adaptable flow and pressure ranges to meet evolving workload demands
- Thermal load balancing across grouped RCD units
- Local and remote HMI for monitoring and system control
- Integration via Modbus, OPC UA, and SNMP and Redfish
- Intelligent load distribution across multiple CDUs
- Heat rejection range from 300 kW up to 2,000 kW per unit
- Compact footprint delivering 129 kW per ft² (0.3 m²)
- Optimized for targeted AI and HPC cluster deployments
EcoCore RCD Technical Specifications
| Category | RCD Specifications |
|---|---|
| Cooling Capacity per Module | 300kW to 2500 kW |
| Approach [ATD] | 4°C [7.2°F] |
| Maximum TCS Flow | 60 L/S (951 GPM) |
| TCS Pressure Head at Maximum Flow | 2.3 Bar [33 PSI] ( 5 bar [73 psi ] total available head) |
| Dimensions | 1.2 m × 1.2 m × 2.3 m (3.9 ft × 3.9 ft × 7.6 ft) |
| Power | 400V - 480V 50-60Hz 3-phase dual feeds |
| Maximum Power Consumption | 32kW |
| Primary Coolant Type (FWS) | Process Water Water-Glycol Mix [1-25%] |
| Secondary Coolant Type (TCS) | Process Water Water-Glycol Mix [1-25%] |
| Primary Connection | 150 mm [6 in.] Sanitary, SS316 |
| Secondary Connection | 150 mm [6 in.] Sanitary, SS316 |
| TCS Filtration | 25µm Full-Stream |
| FWS Filtration (Optional) | 500µm Full-Stream |
| Redundancy | N+1 Pump and Filter |
| Integrated Degasser | Yes |
| Linked System Operation | 2 to 6 CDU Modules |
| Communication | Modbus, OPC UA, SNMP, Redfish |
View Our Other Solutions
FAQs
What is the EcoCore RCD?
The EcoCore RCD is a rack-level Cooling Distribution Unit that delivers localized, high-density cooling directly to servers. It is designed for AI-ready and high-performance compute environments.
How much cooling capacity does the EcoCore RCD provide?
The EcoCore RCD offers between 300 kW and 2,500 kW of cooling per module. This capacity supports today’s densest compute clusters while allowing for future expansion.
What cooling methods does the EcoCore RCD support?
The EcoCore RCD supports both liquid-to-liquid (L2L) and liquid-to-air (L2A) cooling. This flexibility makes it adaptable for different data center requirements and workloads.
What are the flow, pressure, and connection specifications of the EcoCore XCD?
The EcoCore RCD uses a modular design that allows operators to link multiple CDU units. This scalability ensures that cooling capacity grows with compute demand.
What makes the EcoCore RCD reliable?
The EcoCore RCD includes N+1 redundancy for pumps and filtration. It also features integrated degassing and load balancing across units, ensuring continuous uptime and efficiency.