Rear Door Heat Exchangers vs. Direct Liquid Cooling with a CDU

Rear door heat exchangers (RDHx) and direct-to-chip liquid cooling both put water near the rack, so they often get grouped together. They remove heat at different points. An RDHx cools the air after it leaves the servers. Direct liquid cooling (DLC) takes heat off the processor through a cold plate before it ever reaches the air. That difference sets the density each can support and the infrastructure each needs.

How a rear door heat exchanger works

An RDHx replaces the back door of a rack with a coil. Server fans push hot exhaust air through the coil, chilled water inside absorbs the heat, and cooler air returns to the room. Passive doors rely on server fans alone. Active doors add their own fans to move more air.

The servers stay air-cooled. Nothing inside the IT equipment changes, which is why RDHx is a common first step for operators adding density to an existing air-cooled hall.

How direct liquid cooling with a CDU works

In DLC, a cold plate sits on each processor and other hot components. Coolant flows through the plates, picks up heat directly from the silicon, and returns through rack manifolds. A coolant distribution unit (CDU) manages that technology cooling system (TCS) loop. It controls flow, pressure and temperature, filters the coolant, and transfers the heat to facility water through a heat exchanger.

The CDU keeps the server loop clean and isolated from the building’s water. That separation protects cold plates with very fine channels from scale and debris.

Where each one runs out of room

RDHx capacity is limited by how much heat the server fans can push through the coil. Air carries far less heat per unit volume than water, so the coil and fans set a ceiling on rack density. Published vendor figures put rear doors at roughly 20 to 80 kW per rack, and the largest active doors on the market are rated up to about 120 kW.

DLC removes most of the heat at the chip, so rack density can climb well past what air can handle. Current AI platforms are designed around liquid cooling at the chip level. NVIDIA’s GB200 NVL72, for example, draws about 120 kW per rack and requires liquid cooling. Some heat still goes to air from memory, drives and power supplies, so DLC halls usually keep some air cooling for the remainder.

Water temperature and efficiency

Because a cold plate touches the heat source, DLC can run on warmer coolant than a rear door coil. Warmer supply water means more hours when outdoor air or a natural water source can cool the facility loop without chillers. A CDU with a low approach temperature, the gap between facility water in and TCS water out, widens that window further.

RDHx coils generally need cooler water to remove heat from air, which means more chiller hours.

Choosing between them

RDHx fits when:

  • The servers are air-cooled and will stay that way.
  • Rack density is rising but stays in a range the coil can handle.
  • You need to add cooling to an existing hall with little construction.

DLC with a CDU fits when:

  • The hardware is designed for cold plates, as most current AI accelerators are.
  • Rack density is beyond what an air path can carry.
  • You want warmer water and more free cooling hours.
  • You are building new capacity and can plan rack manifolds and TCS piping from the start.

Many halls will run both for a while, with RDHx on legacy air-cooled racks and DLC on new AI racks. Plan the facility water loop so it can serve both without forcing the DLC side down to the colder temperatures the doors need.

Planning a move from air to liquid? Ask Nautilus engineering how a CDU fits your existing facility water loop.

More Recent Posts

Facility-wide CDUs with red and blue coolant piping serving rows of AI servers

Facility-Wide CDUs for AI Data Centers

TL;DR – A facility-wide coolant distribution unit connects the liquid-cooling loop serving AI hardware to the data center’s heat-rejection infrastructure. It gives operators centralized control

Scroll to Top

Nautilus Data Technologies Named NVIDIA AI Factory Infrastructure Partner