In a direct-to-chip cooling system, the coolant distribution unit (CDU) is the piece of equipment between the building’s water and the servers. Cold plates pull heat off the processors, but the CDU decides what coolant reaches those plates, how much of it, how hot and at what pressure. If the CDU stops, high-density racks lose cooling almost immediately and begin to throttle or shut down.
The CDU separates two loops
A direct-to-chip system has two water circuits. The facility water system (FWS) is the building loop, fed by chillers, dry coolers, cooling towers or a natural water source. The technology cooling system (TCS) is the closed loop that runs through the rack manifolds and cold plates.
The CDU connects them through a heat exchanger. Heat moves from the TCS into the facility water, and the two fluids never mix. That matters because cold plates have very fine internal channels. Facility water can carry scale, sediment and biological growth that would clog them. The TCS stays a small, clean, treated volume.
The CDU controls temperature
Server and chip makers specify a coolant supply temperature range for the cold plates. The CDU keeps the TCS supply inside that range as IT load and facility water temperature change through the day. It does this by modulating its primary supply valve, which sets how much facility water flows through the heat exchanger, and by adjusting the speed of its TCS pumps.
The gap between the facility water entering the CDU and the TCS coolant leaving it is called the approach temperature. A smaller approach lets the facility run warmer water for the same supply temperature at the chip. Warmer facility water means more hours of free cooling and fewer chiller hours.
The CDU moves coolant at the right flow and pressure
CDU pumps push coolant through the TCS loop. Each rack manifold, quick disconnect and cold plate adds pressure drop, and the CDU has to overcome all of it while delivering the flow each rack needs. When you compare CDUs, check the available pressure at the flow your design requires. The maximum flow on the datasheet tells you much less.
Most CDUs use multiple pumps so one can be serviced or fail without stopping flow. Ask whether the pumps run together, sharing load, or whether one waits in standby.
The CDU keeps the coolant clean
Filtration in the CDU catches particles before they reach the cold plates. Many units also monitor coolant quality, including conductivity and pH, and alert operators when the fluid needs attention.
The CDU watches for problems
A CDU’s controls track supply and return temperatures, flow, pressure, pump status and filter condition. Leak detection and integration with the building management system (BMS) or data center infrastructure management (DCIM) software let operators see a fault before it affects the racks.
Questions to ask a CDU vendor
- What approach temperature does the unit achieve at my design flow?
- How much pressure is available at the rack at that flow?
- What redundancy does the pump and controls design provide, and can the unit be serviced while running?
- Which facility water sources is the heat exchanger rated for?
- How does the unit report to our BMS or DCIM?